The point where the environmental state changes from abnormal to
normal and users receive a clearing event notification. The function of
Hysteresis is to avoid receiving multiple event notifications.
*For high threshold, the point is the threshold minus the
Hysteresis value; for low threshold, the point is the threshold
plus the Hysteresis value.
For example: The high threshold is 32°C, and hysteresis is 2°C.
The temperature rises to 33°C, you will get a warning. Then
it goes down to 31°C and up to 33°C repeatedly. No clearing
events and warnings will occur while the temperature readings
are within the Hysteresis. You will not get a clearing event until
it drops to 30°C.
Define the abnormal change of temperature per 5 minutes.
For example: The current temperature is 23°C, and rate of
change is 10°C. If it goes up to 33°C or down to 13°C within 5
minutes, you will get a warning.
Enter the name of each input dry contact relay and use the dropdown
menu to define the normal status of each one.