43
Web Interface
Intelligent PDU User Guide
Outlet Configuration Page
Item
Definition
Name
The name entered by the user to identify the selected outlet or multiple
outlet configuration.
Action Configuration
Power On/Off
Delay
*Instant: Turn on/off the outlet immediately.
*Delay: Delay time before turning on/off the outlet. Valid values
are within the range of 1 to 7,200 seconds.
*Never: Never turn on/off the outlet.
Reboot Duration
The length of time the outlet will remain off during a Reboot action. Valid
values are within the range of 5 to 60 seconds.
Load Configuration
Overload
Threshold
Set the value for individual outlet that will signal an overload warning in
Watts. Must be higher than Near Overload Threshold.
Near Overload
Threshold
Set the value for individual outlet that will signal a near overload
warning in Watts. Must be between Overload Threshold and Low Load
Threshold.