Copyright © 2019 Cyber Power Systems, Inc. All rights reserved. K01-C000483-01
Yellow
ON Beep twice every 30 seconds Battery Mode The UPS is providing battery power.
Flash Rapid Beeping Low Battery The UPS will run out of battery power soon.
Red
ON, Flash once
every 5 seconds
Constant Tone Battery Output Short Fault
Turn off the UPS and unplug at least one piece of
equipment.
ON, Flash twice
every 5 seconds
Constant Tone Overload Fault
Connected equipment exceeds the rating of the unit.
Turn off the UPS and unplug at least one piece of
equipment.
ON, Flash 3 times
every 5 seconds
Constant Tone Charger Fault Contact CyberPower for support
ON, Flash 4 times
every 5 seconds
Constant Tone Hardware Fault Contact CyberPower for support
Flash Constant Tone Overload Warning
Connected equipment exceeds the rating of the unit.
Turn off the UPS and unplug at least one piece of
equipment.
TECHNICAL SPECIFICATIONS
TROUBLESHOOTING
Problem Possible Cause Solution
The UPS does not perform
expected runtime.
Batteries are not fully charged. Recharge the battery by leaving the UPS plugged in.
Battery is slightly worn out. Contact CyberPower Systems Technical Support.
The UPS will not turn on.
The unit is not connected to an AC outlet. The unit must be connected to a 220-240V outlet.
The battery is worn out. Contact CyberPower Systems Technical Support.
Mechanical problem. Contact CyberPower Systems Technical Support.
Outlets do not provide
power to equipment.
Fuse is blown or breaker is tripped due to
overload.
Turn the UPS off and unplug at least one piece connected equipment. Unplug
the power cord of the UPS then replace the blown fuse with a spare one or
press the circuit breaker knob. Connect power cord then turn the UPS on.
Make sure that your spare fuse meets the specification.
Batteries are discharged. Allow the unit to recharge for at least 4 hours.
Unit has been damaged by a surge or
spike.
Contact CyberPower Systems Technical Support.
For more information, visit www.cyberpower.com
All rights reserved. Reproduction without permission is prohibited.
Model
UT650EG UT800EG UT1050EG
Capacity (VA/W)
650/360 800/400 1050/630
Input
Voltage Range
165~290Vac
Nominal Frequency
50/60Hz +/-5Hz
Output
On Battery Output Voltage
220/230/240Vac
On Battery Output Frequency
50/60Hz +/-1%
Overload Protection
Fuse Fuse Circuit Breaker
Physical
Total UPS Receptacles
Universal x 3 Universal x 3 Universal x 4
Dimensions (W x H x D)(mm)
84 x 174 x 280 84 x 174 x 280 95 x 220 x 307
Weight
3.8 kg 4.0 kg 6.9 kg
Battery
Sealed Maintenance Free Lead Acid Battery
RBP0119 x1 RBP0143 x1 RBP0119 x2
Typical Recharge Time
6 Hours to 90% from total discharge
Warning Diagnostics
Indicators
Utility / Battery / Fault
Audible Alarms
On Battery, Low Battery, Overload, Fault
Environmental
Operating Temperature
0C to 40C
Operating Relative Humidity
0 to 90%