EasyManua.ls Logo

Cylon CBX-8R8-H - User Manual

Default Icon
14 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
DS0119 rev 40 ©2018 Cylon All Rights Reserved. Subject to change without notice
WWW.CYLON.COM
WWW.CYLON-AUTOMATRIX.COM
page 1 of
14
TECHNICAL DATASHEET & INSTALLATION GUIDE
CBX System
CBX System
CBX-8R8|CBX-8R8-H|FLX-4R4|FLX-4R4-H|FLX-8R8|FLX-8R8-H|FLX-16DI
DESCRIPTION
The CBX-8R8(-H) is a fully programmable BTL-listed BACnet®
Advanced Application Controller (B-AAC) that communicates on
an RS-485 local area network using the BACnet® MS/TP protocol.
This controller features 8 UniPuts™ with Relay and 8 Universal
Inputs as well as support for up to three FLX (Field Level
eXpansion) series extension modules providing up to 64 points
of control. FLX expansion modules are available in a variety of
options to allow maximum flexibility in achieving the required
point configuration.
The CBX-8R8(-H) is designed for a wide range of applications for
intelligent control of HVAC equipment, lighting control, and
electrical systems including metering applications.
APPLICATION
The CBX-8R8(-H) is suitable for controlling various equipment
such as; air handling units, boilers, chillers, cooling towers, pump
systems, central plant equipment, variable frequency drives,
lighting control and metering. The controller supports multi-
protocol communications simultaneously including BACnet®
MS/TP and Modbus® RTU.
The fully programmable CBX-8R8(-H) can be tailored to meet a
variety of applications by creating and modifying strategies using
Cylon's CXpro
HD
programming interface.
Product Selection Chart
Part Number
Module
Service
UniPuts
TM
with Relay
1
Universal
Inputs
Digital
Inputs
Modbus
RTU
Devices
CBT-STAT
Bus
Switch
& Pot.
Aux
Power
FLX
I/O
Modules
CBX-8R8
Main
Controller
8 8 0 4
*
1
3
CBX-8R8-H
Main
Controller
8 8 0 4
*
1
3
FLX-4R4
Expansion
Module
4 4 0 0 0
-
FLX-4R4-H
Expansion
Module
4 4 0 0 0
-
FLX-8R8
Expansion
Module
8 8 0 0 0
-
FLX-8R8-H
Expansion
Module
8 8 0 0 0
-
FLX-16DI
Expansion
Module
0 0 16 0 0
-
Note: 1 UniPuts
TM
are software configurable for point types AI, DI, AO or DO-R.
Note: * CBX Modbus® RTU supports a total of 40 points across 4 devices
CBX-8R8
8 UniPuts™ + Relays
hardware connections that can be used as
inputs, outputs or relays (software selectable)
8 Universal Inputs
CBX-8R8-H
Including Hand/Off/Auto Local Override
Function
Field Level eXpansion Modules
FLX-4R4
4 UniPuts™ with Relay
4 Universal Inputs
FLX-8R8
8 UniPuts™ with Relay
8 Universal Inputs
FLX-16DI
16 Digital Inputs
FLX-4R4-H, FLX-8R8-H
Including Hand/Off/Auto Local Override
Function
Support for Cylon smart thermostat bus
LED status on all I/O channels provides
indication of fault or override status
Compact form factor to maximize enclosure
space
Scalable from 16 points to 64 points using FLX
modules
Easy module expansion using simple bus
connectors
Up to 64 Trendlogs, 1024 entries per Trendlog
Accurate Universal Inputs support a variety of
thermistors and RTDs that range from 0 to 450 kΩ
INSTALLATION GUIDE : see page 5
Question and Answer IconNeed help?

Do you have a question about the Cylon CBX-8R8-H and is the answer not in the manual?

Summary

Specifications

Mechanical Specifications

Details on size, enclosure material (Flame-Retardant ABS), and DIN rail mounting.

Connection Details

Information on terminals, conductor area, and environmental considerations.

Electrical Requirements

Supply voltage, power ratings for CBX and FLX modules, and auxiliary power.

Processor and Communications

Details on processor type, clock speed, memory, and communication ports (MS/TP, Modbus).

Software and Interface

Overview of software features like strategy blocks, trendlogs, and engineering software (CXproHD).

Dimensions and Wiring Diagrams

Product Dimensions

Visual representation of physical dimensions for CBX-8R8 and FLX modules.

Installation Guide: Terminals

Installation Guide: Configuration

Installation Guide: Network Setup

Setting CBX MS;TP Address

Instructions on setting the MS/TP address using DIP switch or software selection.

Connecting to MS;TP Network

Guidance on wiring RS-485 communication, daisy-chaining, and network termination.

Configuration and FLX Module Connection

Adding Controllers and Configuring Strategy

Strategy Configuration Details

Setting Up Controller Strategy

Creating or editing controller strategies using CXproHD, including strategy blocks and points.

Output Override Functionality

Hardware Override Controls

Location and function of override switches (Manual, Auto, Off) for HOA variants.

Override Point in Strategy

How the controller strategy detects and reacts to manual overrides.

Cylon CBX-8R8-H Specifications

General IconGeneral
BrandCylon
ModelCBX-8R8-H
CategoryController
LanguageEnglish