DS0119 rev 40 ©2018 Cylon All Rights Reserved. Subject to change without notice
WWW.CYLON.COM
WWW.CYLON-AUTOMATRIX.COM
page 1 of
14
TECHNICAL DATASHEET & INSTALLATION GUIDE
CBX System
CBX System
CBX-8R8|CBX-8R8-H|FLX-4R4|FLX-4R4-H|FLX-8R8|FLX-8R8-H|FLX-16DI
DESCRIPTION
The CBX-8R8(-H) is a fully programmable BTL-listed BACnet®
Advanced Application Controller (B-AAC) that communicates on
an RS-485 local area network using the BACnet® MS/TP protocol.
This controller features 8 UniPuts™ with Relay and 8 Universal
Inputs as well as support for up to three FLX (Field Level
eXpansion) series extension modules providing up to 64 points
of control. FLX expansion modules are available in a variety of
options to allow maximum flexibility in achieving the required
point configuration.
The CBX-8R8(-H) is designed for a wide range of applications for
intelligent control of HVAC equipment, lighting control, and
electrical systems including metering applications.
APPLICATION
The CBX-8R8(-H) is suitable for controlling various equipment
such as; air handling units, boilers, chillers, cooling towers, pump
systems, central plant equipment, variable frequency drives,
lighting control and metering. The controller supports multi-
protocol communications simultaneously including BACnet®
MS/TP and Modbus® RTU.
The fully programmable CBX-8R8(-H) can be tailored to meet a
variety of applications by creating and modifying strategies using
Cylon's CXpro
HD
programming interface.
Product Selection Chart
Part Number
Module
Service
UniPuts
TM
with Relay
1
Universal
Inputs
Digital
Inputs
Modbus
RTU
Devices
CBT-STAT
Bus
Switch
& Pot.
Aux
Power
FLX
I/O
Modules
CBX-8R8
Main
Controller
8 8 0 4
*
1
3
CBX-8R8-H
Main
Controller
8 8 0 4
*
1
3
FLX-4R4
Expansion
Module
4 4 0 0 0
-
FLX-4R4-H
Expansion
Module
4 4 0 0 0
-
FLX-8R8
Expansion
Module
8 8 0 0 0
-
FLX-8R8-H
Expansion
Module
8 8 0 0 0
-
FLX-16DI
Expansion
Module
0 0 16 0 0
-
Note: 1 UniPuts
TM
are software configurable for point types AI, DI, AO or DO-R.
Note: * CBX Modbus® RTU supports a total of 40 points across 4 devices
CBX-8R8
8 UniPuts™ + Relays
hardware connections that can be used as
inputs, outputs or relays (software selectable)
8 Universal Inputs
CBX-8R8-H
Including Hand/Off/Auto Local Override
Function
Field Level eXpansion Modules
FLX-4R4
4 UniPuts™ with Relay
4 Universal Inputs
FLX-8R8
8 UniPuts™ with Relay
8 Universal Inputs
FLX-16DI
16 Digital Inputs
FLX-4R4-H, FLX-8R8-H
Including Hand/Off/Auto Local Override
Function
Support for Cylon smart thermostat bus
LED status on all I/O channels provides
indication of fault or override status
Compact form factor to maximize enclosure
space
Scalable from 16 points to 64 points using FLX
modules
Easy module expansion using simple bus
connectors
Up to 64 Trendlogs, 1024 entries per Trendlog
Accurate Universal Inputs support a variety of
thermistors and RTDs that range from 0 to 450 kΩ
INSTALLATION GUIDE : see page 5
Question and Answer IconNeed help?

Do you have a question about the Cylon FLX-8R8 and is the answer not in the manual?

Summary

Technical Specifications

Inputs and Outputs Specifications

Configuration and range details for UniPuts, Universal, and Digital Inputs.

Installation Guide: Terminals

Installation Guide: Indicator LEDs

Installation Guide: MS;TP Addressing

Installation Guide: Network Configuration

BACnet Communications Configuration

Default settings and configuration steps for BACnet communications.

Installation Guide: FLX Bus Setup

Installation Guide: Software Configuration

Installation Guide: Controller Strategy

Setting Up the Controller Strategy

Guidance on creating and adding strategy blocks and points in CXproHD.

Operation: Inputs and Outputs

Universal and UniPuts Inputs

Details on configuring and using Universal Inputs and UniPuts terminals.

Operation: Output Modes

UniPuts Output Modes

Details on analog and digital output modes for UniPuts terminals.

Operation: Output Override

Hardware Output Override Controls

How to use hardware override switches for outputs (HOA variants).

Cylon FLX-8R8 Specifications

General IconGeneral
BrandCylon
ModelFLX-8R8
CategoryController
LanguageEnglish