Establish whether the access code has the authorization to activate
command outputs (maximum 4) and the number of outputs to be activated.
This function is valid only when the Link type is selected in the OUTPUTS
menu of Installer Menu.
Press to return to the access code selection menu. Step 5
Then you can continue with programming other access codes, or press to return to the
ACCESS CODES menu from where you can press and to move to the next menu or
press to exit from the Installer Menu.
1.31.3 Configuring Access Code
Setting an Access Code
If you want to set or change an access code, follow the steps described in "1.31.2 Configuring Authority
Level" to enter the NEW CODE submenu.
On the NEW CODE submenu, type in the new code, and then press .
Step 1
The confirmation text "PWD VALID" is shown.
Type in the new code again, and then press to store the new code. Step 2
If the code is not valid or typed incorrectly, the operation will not succeed and two beeps with the
text "PWD INVALID" confirm the error. In this case, repeat the operation correctly.
Press to exit. Step 3
Deleting an Existing Access Code
Access Code 1 cannot be deleted.
On the Access Code submenu, for example, Access Code 2, press and hold for at least Step 1
three seconds.
The "NO PRESENT" message is shown to indicate that the Access Code is deleted.
Press to exit. Step 2
A cancelled access code is no longer operational but can be reactivated by a user with an
appropriate authority level such as Supervisor.