Troubleshooting for Wall Mounted/Floor Standing Type SiUS122226E
162 Part 6 Service Diagnosis
Reference
5.4 Thermistor or Related Abnormality
Error Code C4, C9
Method of Error
Detection
The temperatures detected by the thermistors determine thermistor errors.
Error Decision
Conditions
The voltage between the both ends of the thermistor is either 4.96 V or more, or 0.04 V or less with
the power on.
Supposed
Causes
Disconnection of connector
Defective thermistor(s)
Defective indoor unit PCB
Troubleshooting
C4 : Indoor heat exchanger thermistor
C9 : Room temperature thermistor
Check No.01 Refer to P.224
YES
(R21870)
NO
Check No. 01
Check the thermistor resistance
value.
YES
NO
Caution
Correct the connection.
Replace the defective
thermistor(s).
Replace the indoor unit PCB
(control PCB).
Normal?
Normal?
Check the connection of
connectors.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.

Table of Contents

Other manuals for Daikin 2MXL18WMVJU9

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXL18WMVJU9 and is the answer not in the manual?

Daikin 2MXL18WMVJU9 Specifications

General IconGeneral
BrandDaikin
Model2MXL18WMVJU9
CategoryAir Conditioner
LanguageEnglish

Related product manuals