SiUS121736EA Control Specification
Functions and Control 104
4.13 Electronic Expansion Valve Control
Outline The following items are included in the electronic expansion valve control.
Electronic expansion valve is fully closed
1. Electronic expansion valve is fully closed when turning on the power.
2. Pressure equalizing control
Room Distribution Control
1. Gas pipe isothermal control
2. SC (subcooling) control
3. Liquid pipe temperature control (with all ports connected and all rooms being air-conditioned)
4. Liquid pipe temperature control for stopped rooms
5. Dew prevention control for indoor rotor
Open Control
1. Electronic expansion valve control when starting operation
2. Electronic expansion valve control when the frequency changes
3. Electronic expansion valve control for defrosting
4. Electronic expansion valve control for oil recovery
5. Electronic expansion valve control when a discharge pipe temperature is abnormally high
6. Electronic expansion valve control when the discharge pipe thermistor is disconnected
7. Electronic expansion valve control for indoor unit freeze-up protection
Feedback Control
Target discharge pipe temperature control

Table of Contents

Other manuals for Daikin 2MXS18NMVJUA

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Daikin 2MXS18NMVJUA and is the answer not in the manual?

Daikin 2MXS18NMVJUA Specifications

General IconGeneral
RefrigerantR-410A
Cooling Capacity18000 BTU
Power Supply208/230V, 60Hz
Indoor Unit Dimensions (W x H x D)Varies by indoor unit model
Indoor Unit WeightVaries by indoor unit model
Operating Temperature (Cooling)14°F to 115°F

Related product manuals