OMM 1166-1 AGZ 025D through 190D 51
Screen U-14
From Screen U-4, U11
Set-Up
No password
Operator
Links to screen
Available Modes
R
Start Up DT
R
Shut Down DT
R
Max Pulldown Rate
R
Stage Up Delay
R
Stage Down Delay
R
Start To Start Delay
Stop To Start Delay
Ice Cycle Delay
R
External Fault Config
Display Units
Screen U-15
From Screen U-4
Temperatures
No password
Operator
Links to screen
Evap Leaving Water Temp
R
Evap Entering Water Temp
R
Evaporator Delta T
R
Active Set Point
R
Start Up Temperature
R
Shut Down Temperature
R
Stage Up Temperature
R
Stage Down Temperature
R
Pulldown Rate
Outside Air Temperature
R
Cool LWT Setpoint 1
R/W
Cool LWT Setpoint 2
R/W
Ice LWT Setpoint
R/W
Screen U-16
From Screen U-4, U-11
Date/Time/Schedules
No password
Operator
Links to screen
Actual Time
R/W
Actual Date
R/W
UTC Difference
R/W
DLS Enable
R/W
DLS Start Month
R/W
DLS Start Week
R/W
DLS End Month
R/W
DLS End Week
R/W
Screen U-17
From Screen U-4, U-11
Power Conservation
No password
Operator
Links to screen
Unit Capacity
R
Demand Limit Enable
R/W
Demand Limit Value
R
LWT Reset Enable
R/W
Continued next page.