EasyManua.ls Logo

Daikin AGZ210E User Manual

Daikin AGZ210E
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Installation, Operation,
and Maintenance Manual
Trailblazer
Air-Cooled Scroll Chillers
Model AGZ, E Vintage
30 to 240 Tons (100 to 840 kW)
HFC-410A Refrigerant
50/60 Hz
IOM 1206-7
Group: Chiller
Part Number: IOM1206-7
Date: July 2016

Questions and Answers:

Daikin AGZ210E Specifications

General IconGeneral
BrandDaikin
ModelAGZ210E
CategoryChiller
LanguageEnglish

Summary

Installation and Application Information

Operating and Standby Limits

Specifies the temperature and pressure ranges for unit operation and standby.

Chilled Water Piping

Requirements for field-installed water piping, including strainers, flow switches, and support.

Water Flow Limitations

Explains constant and variable evaporator flow, and limits to prevent damage and ensure performance.

Evaporator Freeze Protection

Methods and components used to protect the evaporator from freezing in low ambient conditions.

High Ambient Operation

Requirements for units operating in high ambient temperatures, including optional packages.

Electrical Data

Panel High Short Circuit Current Rating

Information on the short circuit current rating of the control panel enclosure.

Unit Controller Operation

Controller Inputs and Outputs

Details on analog and digital inputs and outputs for main controller, compressor modules.

Set Points

How set points are configured, adjusted, and stored in the unit controller.

Circuit Level Set Points

Set points specific to individual refrigerant circuits for fine-tuning operation.

Sequence of Operation

Unit Sequence of Operation - Cool Mode

Step-by-step process for chiller operation in cooling mode, including enabling and flow checks.

Unit Sequence of Operation - Ice Mode

Step-by-step process for chiller operation in ice mode, including delays and flow checks.

Circuit Sequence of Operation

Detailed sequence for individual circuit operation, including enabling, starting, and stopping compressors.

Unit Functions

Unit Enable

Conditions and set points required for enabling the chiller to operate.

Unit Capacity Control

Methods for controlling unit capacity, including compressor staging and overrides.

RapidRestore® Option

Features and operation of the RapidRestore® option for quick restart and loading.

Circuit Functions

Circuit Control Logic

Conditions for circuit enabling and compressor availability for starting and running.

EXV Control

Control states (Closed, Superheat) and operation of the electronic expansion valve.

Superheat Target

How the suction superheat target is selected based on circuit capacity and compressor status.

Alarms

Unit Fault Alarms

Faults that cause rapid stops, including PVM/GFP, flow loss, freeze protect, and sensor faults.

Circuit Fault Alarms

Faults specific to a circuit, such as low/high pressure conditions and sensor failures.

Mechanical High Pressure Switch

Trigger conditions and actions for the mechanical high pressure switch alarm.

Using the Controller

Passwords

Procedures for entering passwords to access different parameter levels.

Startup and Shutdown Procedures

Startup

Essential steps for initiating chiller operation, including setpoint verification and pump activation.

Shutdown

Procedures for temporary and extended shutdowns to protect the unit and system.

Unit Maintenance

Filter-Driers

When to replace filter-driers based on pressure drop or moisture indication in the sight glass.

Refrigerant Charging

Step-by-step procedures for recharging the unit with R-410A refrigerant, including safety precautions.

Troubleshooting Chart

Compressor Will Not Run

Common causes and corrective steps for when the compressor fails to start or run.

Limited Product Warranty

Related product manuals