EasyManua.ls Logo

Daikin AGZ225E User Manual

Daikin AGZ225E
112 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
Installation, Operation,
and Maintenance Manual
Trailblazer
Air-Cooled Scroll Chillers
Model AGZ, E Vintage
30 to 240 Tons (100 to 840 kW)
HFC-410A Refrigerant
50/60 Hz
IOM 1206-7
Group: Chiller
Part Number: IOM1206-7
Date: July 2016

Questions and Answers:

Daikin AGZ225E Specifications

General IconGeneral
BrandDaikin
ModelAGZ225E
CategoryChiller
LanguageEnglish

Summary

Installation, Operation, and Maintenance Manual

Trailblazer™ Air-Cooled Scroll Chillers

Details on the Trailblazer™ Air-Cooled Scroll Chillers, including model numbers and capabilities.

Installation and Application Information

Operating and Standby Limits

Table detailing the maximum and minimum operating and standby ambient and fluid temperatures.

Chilled Water Piping

Requirements and recommendations for field-installed chilled water piping.

Evaporator Freeze Protection

Methods and components used to protect the evaporator from freeze-up.

High Ambient Operation

Requirements for operating the chiller in high ambient temperature conditions.

Pressure Drop Data

Table 11: Pressure Drop Data

Table detailing pressure drop values for different flow rates and models.

Electrical Data

Table 14: Electrical Data - Single Point (60/50 Hz)

Electrical specifications for single-point connections across various voltages and frequencies.

Table 16: Electrical Data - Single Point (60/50 Hz)

Electrical specifications for single-point connections across various voltages and frequencies.

Table 18: Electrical Data - Multiple Point (60/50 Hz)

Electrical specifications for multiple-point connections across various voltages and frequencies.

Table 20: Electrical Data - Multiple Point (60/50 Hz)

Electrical specifications for multiple-point connections across various voltages and frequencies.

Unit Controller Operation

Controller Inputs and Outputs

Detailed lists of analog and digital inputs and outputs for the main controller and compressor modules.

Set Points

Default and adjustable set point values for unit configuration and operation.

Table 38: Unit Level Set Point Defaults and Ranges

Table of default and adjustable set point ranges for unit-level configurations.

Table 47: Commincation Configuration

Configuration settings for network communication protocols like Lon, BACnet, and Modbus.

Circuit Level Set Points

Set points applicable to individual circuits, including mode, compressor, EXV, and fan controls.

Table 48: Set Points for Individual Circuits

Table detailing set points for individual circuits, covering mode, EXV, and sensor offsets.

Dynamic Set Point Ranges and Defaults

Condenser target and fan stage deadband settings based on configuration groups.

Security

Information on password protection for accessing and changing set points.

Sequence of Operation

Figure 47: Unit Sequence of Operation - Cool Mode

Flowchart illustrating the unit's operational sequence in Cool Mode, from power up to readiness.

Figure 48: Unit Sequence of Operation - Cool Mode (continue)

Continuation of the operational sequence for Cool Mode, detailing capacity increase and load satisfaction.

Figure 49: Unit Sequence of Operation - Cool Mode (continued)

Further steps in Cool Mode sequence, covering capacity decrease and shutdown logic.

Figure 50: Unit Sequence of Operation - Ice Mode

Flowchart detailing the unit's operational sequence in Ice Mode.

Figure 51: Unit Sequence of Operation - Ice Mode (continued)

Continuation of Ice Mode sequence, covering capacity increase and ice cycle completion.

Unit Functions

Unit Enable

Conditions and tables for enabling and disabling the chiller operation.

Freeze Protection

Conditions that trigger evaporator pump start for freeze protection and when it ends.

LWT Target

How the Leaving Water Temperature (LWT) target is selected and adjusted.

Unit Capacity Control

Methods for controlling unit capacity, including compressor staging and limits.

Compressor Staging in Cool Mode

Logic for starting and stopping compressors based on evaporator LWT in Cool Mode.

Staging Sequence

Logic for determining which compressor starts or stops next, balancing circuits.

RapidRestore® Option

Description of the RapidRestore® option for faster restart and loading capabilities.

Circuit Functions

Circuit Control Logic

Conditions required for circuit enabling and compressor availability.

Circuit States

Description of the four circuit states: Off, Preopen, Run, and Pumpdown.

Low Ambient Starts

Initiation and handling of low ambient starts, including timer and alarm logic.

Circuit Status

Table defining circuit status based on various conditions.

Compressor Control

Logic for controlling compressor operation, including starting and stopping.

EXV Control

Control states and operation of the Electronic Expansion Valve (EXV).

Superheat Target

Selection of suction superheat target based on circuit capacity.

Position Commands

Reliability improvements for EXV positioning commands.

Alarms

Unit Fault Alarms

Description of unit fault alarms, including triggers, actions, and resets.

Evaporator Flow Loss

Alarm triggered by loss of evaporator flow, requiring rapid stop of circuits.

Evaporator Water Freeze Protect

Alarm triggered when evaporator LWT drops below freeze protect set point.

Unit Problem Alarms

Alarms related to evaporator pump failures.

Unit Warning Alarms

Warning alarms for external events and input signal issues.

Circuit Fault Alarms

Fault alarms specific to individual circuits.

Alarm Logs

How to access and interpret alarm and event logs.

Using the Controller

Navigating

How to navigate the controller menus using the keypad and wheel.

Passwords

Procedures for entering passwords to access different parameter levels.

Optional Low Ambient Fan VFD

VFD Interface

Description of the VFD controller interface for viewing data and alarms.

Table 83: Types of Alarms, Faults, and Errors

Classification and response to different types of alarms, faults, and errors detected by the VFD.

Startup and Shutdown Procedures

Startup

Procedures for starting the chiller after all pre-startup checks are complete.

Shutdown

Procedures for temporarily and indefinitely shutting down the chiller.

Component Operation

Unit Maintenance

R-410A Refrigerant

Refrigerant Charging

Procedures for recharging the unit with R-410A refrigerant.

Troubleshooting Chart

Warranty Registration Form (Scroll)

VI . MICROTECH SETPOINTS

MicroTech setpoints for various operational parameters.

Limited Product Warranty

DAIKIN APPLIED AMERICAS INC. LIMITED PRODUCT WARRANTY (North America)

Company's warranty terms for defective parts, labor, and exceptions.

Related product manuals