5 Electrical installation
Installation manual
16
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12
# Layout Open the unit
(a)
2 Dual cable power supply (=split power
supply)
Note: This is for example needed for
installations in Germany.
C1: Power supply for the backup heater
(1N~ or 3N~)
C5: Power supply for the rest of the unit
(1N~)
3 Single cable power supply (=combined
power supply)
+
Preferential kWh rate power supply
without separate normal kWh rate power
supply
(b)
C1: Preferential kWh rate power supply
(1N~ or 3N~)
C2: Preferential kWh rate power supply
contact
# Layout Open the unit
(a)
4 Dual cable power supply (=split power
supply)
+
Preferential kWh rate power supply
without separate normal kWh rate power
supply
(b)
C1: Preferential kWh rate power supply
for the backup heater (1N~ or 3N~)
C2: Preferential kWh rate power supply
contact
C5: Preferential kWh rate power supply
for the rest of the unit (1N~)
5 Single cable power supply (=combined
power supply)
+
Preferential kWh rate power supply with
separate normal kWh rate power supply
(b)
NOT ALLOWED
—
6 Dual cable power supply (=split power
supply)
+
Preferential kWh rate power supply with
separate normal kWh rate power supply
(b)
C1: Normal kWh rate power supply for the
backup heater (1N~ or 3N~)
C2: Preferential kWh rate power supply
contact
C3: Separate normal kWh rate power
supply for the hydro (1N~)
C4: Connection of X11Y
C5: Preferential kWh rate power supply
for the compressor (1N~)
(a) See "3.2.1To open the indoor unit"[47].
(b) Types of preferential kWh rate power supply: