5 Electrical installation
Installation manual
17
EGSAH/X06+10UDA9W
Daikin Altherma 3 GEO
4P598591-1A – 2019.12
INFORMATION
Some types of preferential kWh rate power supply require
a separate normal kWh rate power supply to the indoor
unit. This is required in the following cases:
▪ if the preferential kWh rate power supply is interrupted
when active, OR
▪ if no power consumption of the indoor unit is allowed at
the preferential kWh rate power supply when active.
Detail C1: Factory-mounted power supply cable
Wires: 3N+GND, OR 1N+GND
Maximum running current: Refer to name plate on unit.
Connect the factory-mounted power supply cable to a 1N~ or 3N~
power supply.
a
b
Q1DI
L1 L2 L3 N
3N~, 50 Hz, 400 V AC
F1B
1 3 5 7
2 4 6 8
IIII
Q1DI
L N
1N~, 50 Hz, 230 V AC
F1B
1 3 5 7
2 4 6 8
IIII
1N~ 3N~
OR
BRN
BLK
GRY
BLU
YLW/GRN
BRN
BLK
GRY
BLU
YLW/GRN
a Factory-mounted power supply cable
b Field wiring
F1B Overcurrent fuse (field supply). Recommended fuse for
1N~: 4‑pole, 32A fuse, C curve. Recommended fuse for
3N~: 4‑pole, 16A fuse, C curve.
Q1DI Earth leakage circuit breaker (field supply)
Detail C2: Preferential kWh rate power supply contact
Wires: 2×(0.75~1.25mm²)
Maximum length: 50m.
Preferential kWh rate power supply contact: 16VDC
detection (voltage supplied by PCB). The voltage-free contact
shall ensure the minimum applicable load of 15VDC, 10mA.
Connect the preferential kWh rate power supply contact (S1S) as
follows.
INFORMATION
The preferential kWh rate power supply contact is
connected to the same terminals (X5M/9+10) as the safety
thermostat. Thus, the system can have EITHER
preferential kWh rate power supply OR a safety
thermostat.
Detail C3: Separate normal kWh rate power supply
Wires: 1N+GND
Maximum running current: 6.3A
Connect the separate normal kWh rate power supply as follows:
Q3DI
L N
1N~, 50 Hz, 230 V AC
1×
2×
X2M
1×
5
6
L N