4 Installation
Installation manual
11
EABH/X16DF6V+9W
Daikin Altherma 3 H W
4P644479-1 – 2020.12
4.4.4 To connect the backup heater power
supply
CAUTION
If the indoor unit has a tank with a built‑in electrical booster
heater, use a dedicated power circuit for the backup heater
and booster heater. NEVER use a power circuit shared by
another appliance. This power circuit must be protected
with the required safety devices according to the applicable
legislation.
CAUTION
To guarantee the unit is completely earthed, always
connect the backup heater power supply and the earth
cable.
The backup heater capacity can vary, depending on the indoor unit
model. Make sure that the power supply is in accordance with the
backup heater capacity, as listed in the table below.
Backup
heater type
Backup
heater
capacity
Power
supply
Maximum
running
current
Z
max
*6V 2kW 1N~230V
(a)
9A
4kW 1N~230V
(a)
17A
(b)(c)
0.22Ω
6kW 1N~230V
(a)
26A
(b)(c)
0.22Ω
2kW 3~230V
(d)
5A
4kW 3~230V
(d)
10A
6kW 3~230V
(d)
15A
*9W 3kW 3N~400V 4A
6kW 3N~400V 9A
9kW 3N~400V 13A
(a)
6V
(b)
Electrical equipment complying with EN/IEC 61000-3-12
(European/International Technical Standard setting the limits for
harmonic currents produced by equipment connected to public
low-voltage systems with input current >16A and ≤75A per
phase).
(c)
This equipment complies with EN/IEC61000‑3‑11 (European/
International Technical Standard setting the limits for voltage
changes, voltage fluctuations and flicker in public low-voltage
supply systems for equipment with rated current ≤75A) provided
that the system impedance Z
sys
is less than or equal to Z
max
at the
interface point between the user's supply and the public system. It
is the responsibility of the installer or user of the equipment to
ensure, by consultation with the distribution network operator if
necessary, that the equipment is connected only to a supply with
a system impedance Z
sys
less than or equal to Z
max
.
(d)
6T1
Connect the backup heater power supply as follows:
a
b
X6M
F1B
Q1DI
a Factory-mounted cable connected to the contactor of the
backup heater, inside the switch box (K5M)
b Field wiring (see table below)
Model (power
supply)
Connections to backup heater power
supply
*6V (6V: 1N~230V)
1N~, 50 Hz
230 V AC
SWB
4
3
6
5
2
1
K5M
14
13
Q1DI
1
2
3
4
5
6
7
8
F1B
II I I
NL
X6M
BRN
GRY
BLU1
BLU2
*6V (6T1: 3~230V)
SWB
3~, 50 Hz
230 V AC
4
3
6
5
2
1
K5M
14
13
1
2
3
4
5
6
7
8
F1B
II I I
Q1DI
L1 L2 L3
X6M
BRN
GRY
BLU1
BLU2
*9W (3N~400V)
3N~, 50 Hz
400 V AC
SWB
Q1DI
L1 L2 L3 N
1
2
3
4
5
6
7
8
F1B
II I I
X6M
2
1
K5M
4
3
6
5
14
13
BRN
GRY
BLK
BLU
F1B Overcurrent fuse (field supply). Recommended fuse:
4‑pole; 20A; curve 400V; tripping class C.
K5M Safety contactor (in the switch box)
Q1DI Earth leakage circuit breaker (field supply)
SWB Switch box
X6M Terminal (field supply)