c Wire terminal U
V Wire terminal V
W Wire terminal W
CAUTION
Before measuring the compressor motor windings resistance, measure the
resistance of the multimeter probes by holding the probes against each other. If the
measured resistance is NOT 0Ώ, this value MUST be substracted from the measured
winding resistance.
4 Measure the resistance between the compressor motor windings U-V, V-W
and U-W.
Result: All measurements MUST be approximately the same.
Unit Compressor Winding resistance value
(at temperature of 20°C)
Single phase unit M1C 0.343Ω ± 5%
Three phase unit M1C 1.16Ω ± 5%
Compressor motor winding
measurements are correct?
Action
Yes Continue with the next step.
No Replace the compressor, see
"3.7.2Repair procedures"[4140].
5 Measure the continuity of the U, V and W wires between the compressor and
the PCB. If no continuity, correct as needed, see "6.2Wiring diagram"[4314].
6 Connect the Faston connectors to the compressor wire terminals U, V and W