3 | Components
Service manual
145
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
CAUTION
Overheating the compressor pipes (and the oil inside the compressor pipes) will
damage or destroy the compressor.
9 After soldering is done, stop the nitrogen supply after the component has
cooled‑down.
10 Install the compressor thermal protector, see "To install the compressor
thermal protector"[4148].
11 Connect the Faston connectors to the compressor wire terminals U, V and W
VW
U
c Wire terminal U
V Wire terminal V
W Wire terminal W
12 Install the cover of the compressor wire terminals.
a
a Compressor wire terminals cover
13 Install the compressor insulation, see "3.7.2Repair procedures"[4140].
14 Perform a pressure test, see "4.2.1Checking procedures"[4286].
15 Add refrigerant to the refrigerant circuit, see "4.2.2 Repair
procedures"[4291].
Is the problem solved? Action
Yes No further actions required.
No Return to the troubleshooting of the
specific error and continue with the
next procedure.