4 | Third party components
Service manual
293
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Service tool Remark
Recovery cylinder Compatible with the
refrigerant to be
recovered
Vacuum pump 2-stage, equipped with
solenoid valve
2 Setup a vacuum line between recovery unit discharge and the recovery bottle.
Without this additional setup, the discharge line from the recovery device to
the refrigerant cylinder would not have been vacuumed.
3 Connect the vacuum pump, manifold, recovery unit, and refrigerant recovery
cylinder to the service ports of the refrigerant circuit as shown below. Make
sure the stop valves are open.
a
c
d
b e f
c c
g
h
i
j
a Liquid service port
b Gas service port
c Flexible hose
d Manifold
e Recovery unit
f Vacuum pump
g Scale
h Recovery cylinder
i Vacuum setup
j Internal service port