4 | Third party components
Service manual
297
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
(a)
= OFF, = ON, and = flashing.
Result: The recovery mode is activated. The unit opens the electronic expansion
valves.
To deactivate the recovery mode
After recovering refrigerant, deactivate the recovery mode as follows:
# Procedure 7-segments display
(a)
1 Start from the default situation.
2 Select mode 2.
Press and hold BS1 for 5seconds.
3 Select setting 9.
Press BS2 9times.
4 Select value 2.
a Display the current value.
Press BS3 once.
b Change the value to 2.
Press BS2 once.
c Enter the value in the system.
Press BS3 once.
d Confirm.
Press BS3 once.
5 Return to the default situation.
Press BS1 once.
(a)
= OFF, = ON, and = flashing.
Result: The recovery mode is deactivated. The unit returns the electronic
expansion valves to their initial state.
INFORMATION
Power OFF. When power is turned OFF and turned ON again, the recovery mode is
deactivated automatically.
To add refrigerant
1 See the installer reference guide for the correct procedure.
Is the problem solved? Action
Yes No further actions required.
No Perform a pressure test of the
refrigerant circuit, see "4.2.1Checking
procedures"[4286].