  • R
    Rebecca WilsonAug 19, 2025
    What to do if the backup heater operation is not activated in Daikin Altherma EPGA11DAV3 Air Conditioner?
    • Y
      ygonzalezAug 20, 2025
      Check and make sure that: * The backup heater operation mode is enabled. * The backup heater overcurrent fuse has not been turned off; if it has, check the fuse and turn it back on. * The thermal protector of the backup heater has not been activated; if it has, check the water pressure, whether there is air in the system, and the air purge operation, then press the reset button in the switch box.
  • K
    Kevin HansenAug 21, 2025
    What to do if the pressure relief valve opens in Daikin Altherma EPGA11DAV3 Air Conditioner?
    • T
      Trevor RamirezAug 22, 2025
      The pressure relief valve might open because: * The expansion vessel is broken: Replace the expansion vessel. * The valve of the water circuit towards the expansion vessel is closed: Open the valve. * The water volume in the installation is too high: Make sure that the water volume in the installation is below the maximum allowed value. * The water circuit head is too high: Check the installation requirements. The maximum water circuit head is 10 m.
  • I
    icoxAug 25, 2025
    What to do if the pump is making noise in Daikin Altherma EPGA11DAV3?
    • S
      Shawn MillerAug 25, 2025
      The pump in your Daikin Air Conditioner might be making noise because: * There is air in the system: Purge air manually or use the automatic air purge function. * The water pressure at the pump inlet is too low: Check and make sure that the water pressure is >1 bar, the water pressure sensor is not broken, the expansion vessel is NOT broken, the valve of the water circuit towards the expansion vessel is open, and the pre-pressure setting of the expansion vessel is correct.
  • T
    Traci GreenAug 26, 2025
    What to do if the water flow is too low in Daikin Altherma EPGA11DAV3?
    • G
      gmoralesAug 26, 2025
      Check and ensure that: * All shut-off valves of the water circuit are completely open. * The water filter is clean; clean if necessary. * There is no air in the system; purge air if necessary, either manually or using the automatic air purge function. * The water pressure is >1 bar. * The expansion vessel is NOT broken. * The valve of the water circuit towards the expansion vessel is open. * The resistance in the water circuit is NOT too high for the pump.
  • A
    Amanda ColeAug 28, 2025
    What to do if the system is making gurgling noises after commissioning Daikin Altherma EPGA11DAV3 Air Conditioner?
    • C
      Christopher WatsonAug 28, 2025
      The gurgling noises in your Daikin Air Conditioner system might be caused by: * Air in the system: Purge air from the system. * Various malfunctions.
  • G
    gary93Aug 30, 2025
    How to fix failing or blocked pressure relief valve in Daikin Altherma EPGA11DAV3 Air Conditioner?
    • S
      Sarah GarciaAug 30, 2025
      Flush and clean the complete tank including the piping between pressure relief valve and the cold water inlet and replace the pressure relief valve.
  • L
    Laurie Burns MDSep 1, 2025
    What to do if the unit must start up out of its operation range in Daikin Air Conditioner?
    • M
      Mindy Price DDSSep 1, 2025
      If the water temperature is too low, the unit uses the backup heater to reach the minimum water temperature first (15°C). Check and make sure that: * The power supply to the backup heater is correctly wired. * The backup heater thermal protector is NOT activated. * The backup heater contactors are NOT broken.
  • D
    Dale GoldenSep 3, 2025
    What to do if there is air in the Daikin Altherma EPGA11DAV3 Air Conditioner system?
    • A
      amanda86Sep 3, 2025
      Purge air from the system.
  • M
    meyersmichaelSep 6, 2025
    What to do if various malfunctions occur in Daikin Altherma EPGA11DAV3 Air Conditioner?
    • T
      Taylor BurkeSep 6, 2025
      Check if or is displayed on the home screen of the user interface.
  • J
    James FisherSep 8, 2025
    What to do if the water volume in the installation is too low in Daikin Air Conditioner?
    • J
      Janet BurkeSep 8, 2025
      Make sure that the water volume in the installation is above the minimum required value.