AIR HANDLERS INSTALLATION &
OPERATING INSTRUCTIONS
© 2021-2023 Daikin Comfort Technologies Manufacturing, L.P.
19001 Kermier Rd., Waller, TX 77484
www.goodmanmfg.com -or- www.amana-hac.com
P/N: IO-4004C Date: April 2023
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION.
NOTE: SPECIFICATIONS AND PERFORMANCE DATA LISTED HEREIN
ARE SUBJECT TO CHANGE WITHOUT NOTICE
Contents
1 Important Safety Instructions .................................... 2
2 Shipping Inspection ................................................... 3
2.1 Parts ....................................................................... 3
2.2 Handling ................................................................. 3
2.3 Shipping Material Removal..................................... 3
2.3.1 Blower Support Bracket Removal ....................... 3
3 Codes & Regulations ................................................. 3
4 Replacement Parts ..................................................... 4
5 Pre-Installation Considerations ............................... 4
5.1 Preparation ............................................................. 4
5.2 System Matches ..................................................... 4
5.3 Interconnecting Tubing ........................................... 4
5.4 Clearances ............................................................. 4
5.5 Horizontal Applications ........................................... 4
5.6 Access .................................................................... 4
6 Installation Location ................................................... 4
 .................................................. 4
6.2 Horizontal Left Installation ...................................... 5
 5
6.4 Humid Environment Installations ............................ 6
6.4.1 All Installations – Humid Environments ............... 6
 6
6.4.1.3 Horizontal Installations – Humid Environments 6
7 Refrigerant Lines ........................................................ 7
7.1 Tubing Size ............................................................. 7
7.2 Tubing Preparation ................................................. 7
7.3 Tubing Connections ................................................ 7
7.4 Thermal Expansion Valve System Adjustment ....... 9
8 Condensate Drain Lines ........................................... 10
9 Ductwork .................................................................... 11
9.1 Return Ductwork .................................................... 11
10 Return Air Filters ..................................................... 11
11 Electric Heat ............................................................. 11
12 Electrical and Control Wiring ................................. 12
12.1 Building Electrical Service Inspection .................. 12
12.2 Wire Sizing .......................................................... 12
12.3 Maximum Overcurrent Protection (MOP) ............ 12
12.4 Electrical Connections – Supply Voltage ............. 13
12.4.1 Air Handler Only (Non-Heat Kit Models) ........... 13
12.4.2 Air Handler - Non-Circuit Breaker Heat Kits ..... 13

























WARNING
RECOGNIZE THIS SYMBOL
AS A SAFETY PRECAUTION

WARNING
Question and Answer IconNeed help?

Do you have a question about the Daikin AMST60DU14 and is the answer not in the manual?

Summary

Important Safety Instructions

Pre-Installation Considerations

Preparation and Planning

Read instructions, assemble tools, and gather supplies before starting installation.

System Compatibility

Ensure the entire system is manufacturer approved and AHRI listed for proper operation.

Installation Location and Orientation

Upflow Installation

Steps for installing the unit in an upflow configuration.

Refrigerant Lines

Tubing Connections

Connect refrigerant lines using brazing, ensuring proper seal and using heat protection.

Thermal Expansion Valve System Adjustment

Guidelines for adjusting the TXV for optimal superheat and subcooling.

Condensate Drain Lines

Ductwork

Electric Heat

Electrical and Control Wiring

Building Electrical Service Inspection

Verify single-phase supply, measure voltage, and ensure it matches unit requirements.

Wire Sizing

Select wire size based on MCA, NEC/CSA standards, and voltage drop requirements.

Maximum Overcurrent Protection (MOP)

Install NEC/CEC approved overcurrent protection device, sized appropriately for safety.

Supply Voltage Electrical Connections

Low Voltage Connections

Connect thermostat, condenser, and air handler using 24V control voltage wiring.

Speed Tap Adjustment (Taps 1-5)

Adjust blower motor speed taps (1-5) for desired airflow performance.

Selecting Speed Taps 6-9

AMST60 DU1400** Speed Tap Adjustments

Start-Up Procedure

Air Handler Low Voltage Connections

Wiring Diagrams

Start-Up Checklist

Summary

Important Safety Instructions

Pre-Installation Considerations

Preparation and Planning

Read instructions, assemble tools, and gather supplies before starting installation.

System Compatibility

Ensure the entire system is manufacturer approved and AHRI listed for proper operation.

Installation Location and Orientation

Upflow Installation

Steps for installing the unit in an upflow configuration.

Refrigerant Lines

Tubing Connections

Connect refrigerant lines using brazing, ensuring proper seal and using heat protection.

Thermal Expansion Valve System Adjustment

Guidelines for adjusting the TXV for optimal superheat and subcooling.

Condensate Drain Lines

Ductwork

Electric Heat

Electrical and Control Wiring

Building Electrical Service Inspection

Verify single-phase supply, measure voltage, and ensure it matches unit requirements.

Wire Sizing

Select wire size based on MCA, NEC/CSA standards, and voltage drop requirements.

Maximum Overcurrent Protection (MOP)

Install NEC/CEC approved overcurrent protection device, sized appropriately for safety.

Supply Voltage Electrical Connections

Low Voltage Connections

Connect thermostat, condenser, and air handler using 24V control voltage wiring.

Speed Tap Adjustment (Taps 1-5)

Adjust blower motor speed taps (1-5) for desired airflow performance.

Selecting Speed Taps 6-9

AMST60 DU1400** Speed Tap Adjustments

Start-Up Procedure

Air Handler Low Voltage Connections

Wiring Diagrams

Start-Up Checklist

Daikin AMST60DU14 Specifications

General IconGeneral
ModelAMST60DU14
Cooling Capacity (BTU)60, 000
Cooling Capacity (Ton)5
Cooling Capacity (kW)17.6
RefrigerantR-410A
Voltage (V)208/230
Phase1
Dimensions (H x W x D)49.5 x 21.25 x 21.25 inches
Weight210 lbs
TypeAir Handler
Airflow (CFM)Up to 2000
Airflow Rate1, 600 - 2, 000 CFM