EasyManua.ls Logo

Daikin Bluevolution FNA35A - Page 6

Daikin Bluevolution FNA35A
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5 Installation
Installation manual
6
FNA25~60A2VEB(9)
Split system air conditioners
4P456958-1J – 2020.12
A
a
a
b
c
B
d
A Securing the hanger bracket
B Securing the washers
a Washer (accessories)
b Hanger bracket
c1 Nut (field supply)
c2 Double nut (field supply)
d Washer fixing plate (accessory)
Suspension bolt pitch for fastening to the wall:
A
618
500
Class A(mm)
25&35 740
50&60 1140
Minimum floor area
(1)
To determine the minimum floor area, refer to the table or the graph
below.
1 Depending on the amount of the total refrigerant charge in the
system (m), the minimum floor area is (A
min
).
INFORMATION
If the required exact value for the total refrigerant
charge in the system (m) is not listed below, use the
closest higher value.
In case the total refrigerant charge in the system is
>3.9 kg, refer to "To determine the minimum floor
area" in the General safety precaution.
FNA25&35 FNA50&60
m(kg) A
min
(m
2
)
≤1.842 No requirements
1.843 6.2 5.5
1.9 6.4 5.7
2 6.8 6.0
2.1 7.1 6.3
2.2 7.4 6.6
2.3 7.8 6.9
2.4 8.1 7.2
2.5 8.4 7.5
2.6 8.8 7.8
2.7 9.1 8.1
2.8 9.5 8.4
2.9 9.8 8.7
FNA25&35 FNA50&60
m(kg) A
min
(m
2
)
3 10.1 9.0
3.1 10.5 9.3
3.2 10.8 9.6
3.3 11.1 9.9
3.4 11.5 10.2
3.5 11.8 10.4
3.6 12.2 10.7
3.7 12.5 11.0
3.8 12.8 11.3
3.9 13.2 11.6
5
6
7
8
9
10
11
12
13
14
2 2.11.91.8 2.2 2.3 2.5 2.7 2.9 3.1 3.3 3.52.4 2.6 2.8 3 3.2 3.4 3.6 3.8 3.93.7
m [kg]
A
min
[m
2
]
FNA25&35
5
6
7
8
9
10
11
12
13
1.8
1.843
2 2.11.9 2.2 2.3 2.5 2.7 2.9 3.1 3.3 3.52.4 2.6 2.8 3 3.2 3.4 3.6 3.8 3.93.7
m [kg]
FNA50&60
A
min
[m
2
]
1.843
A
min
Minimum floor area
m Refrigerant charge amount in the system
Floor-standing installation
A Maintenance area width
B Air inlet grille width
a Air outlet direction
b Air inlet grille height
c Air inlet direction
Class A(mm) B(mm)
25&35 1350 660
50&60 1750 1060
(1)
Only for units using R32 refrigerant in combination with a user interface BRC1H52*. Refer to the outdoor unit specifications for the type of
refrigerant to be used.

Related product manuals