Installation manual
4
BRC1D527
Remote controller
4PW16769-1
Example
If during group setting and the time to clean the air
filter is set to FILTER CONTAMINATION - HEAVY,
SET MODE NO. to “10”, FIRST CODE NO. to “0”, and
SECOND CODE NO. to “02”.
Notes
NOTE 1. Setting is carried out in the group
mode, however, if the mode number
inside the parentheses is selected,
indoor units can also be set
individually.
2. The SECOND CODE number is set to
“01” when shipped from the factory.
3. Do not make any settings not given in
the table.
4. Not displayed if the indoor unit is not
equipped with that function.
5. When returning to the normal mode,
88 may be displayed in the LCD in
order for the remote controller to
initialize itself.
6. It is not possible to change field
settings on the remote controller that
is set to “sub”.