ERROR INDICATOR
! NOTE
The LED will blink if error occurred.
If there is any abnormal condition detected, BRC51D64/65 controller will blink the error code. The
format for the error code will be as following:
E01 Require manual reset E19 Indoor coil sensor 4 short
E02 Compressor 1 high temperature (overload) E20 Indoor coil sensor 1 open
E03 Compressor 2 high temperature (overload) E21 Indoor coil sensor 2 open
E04 Compressor 3 high temperature (overload) E22 Indoor coil sensor 3 open
E05 Compressor 4 high temperature (overload) E23 Indoor coil sensor 4 open
E06 Compressor 1 high pressure trip / contact open E24 Outdoor coil sensor 1 short
E07 Compressor 2 high pressure trip / contact open E25 Outdoor coil sensor 2 short
E08 Compressor 3 high pressure trip / contact open E26 Outdoor coil sensor 3 short
E09 Compressor 4 high pressure trip / contact open E27 Outdoor coil sensor 4 short
E10 Compressor 1 trip / low R-22 / outdoor abnormal E28 Outdoor coil sensor 1 open
E11 Compressor 2 trip / low R-22 / outdoor abnormal E29 Outdoor coil sensor 2 open
E12 Compressor 3 trip / low R-22 / outdoor abnormal E30 Outdoor coil sensor 3 open
E13 Compressor 4 trip / low R-22 / outdoor abnormal E31 Outdoor coil sensor 4 open
E14 Room sensor short E32 Compressor 1 de-ice
E15 Room sensor open E33 Compressor 2 de-ice
E16 Indoor coil sensor 1 short E34 Compressor 3 de-ice
E17 Indoor coil sensor 2 short E35 Compressor 4 de-ice
E18 Indoor coil sensor 3 short
1-OM-BRC51D-1117(0)-DAIKIN-EN.in5 5 5/31/18 9:14:42 AM