5. BACnet® Server Gateway Points List
8 Quick User Guide DCM014A51
Object Name
Number of valid digits
Celsius Fahrenheit
“Room Temperature” One decimal place One decimal place
"Occ Cooling Setpoint" "Occ Heating Setpoint"
"Unocc Cooling Setpoint" "Unocc Heating Setpoint"
"Max Cooling Setpoint" "Min Cooling Setpoint"
"Max Heating Setpoint" "Min Heating Setpoint"
One decimal place Integer
"Min Setpoint Differential (Cooling & Heating)” Integer Integer
*3: When the Out_Of_Service property is TRUE, the setting items (Setback Temperature (Cool/Heat), Min Setpoint Differential (Cooling &
Heating) that are mapped to the object are disabled; therefore, a value set on the indoor unit management point remains unchanged
even if Present_Value is changed.
*4: The Out_Of_Service property of "Max Cooling Setpoint" and "Min Cooling Setpoint" indicates the upper and lower limit of the Cool
Setpoint change along with the Present_Value.
(When the Out_Of_Service property of either one is changed from FALSE TRUE, the Out_Of_Service property of the other one also
changes from FALSE → TRUE)
The "Max Heating Setpoint" and "Min Heating Setpoint" which indicates the upper and lower limit of the Heat Setpoint also behaves in
the same way. When the Out_Of_Service property is TRUE, the setting items (Max and Min Setpoint) mapped to an object are disabled,
so that a value set for the indoor unit management point remains unchanged even when the Present_Value changes.