Why is there no Modbus communication with my Daikin DIII EKMBDXB7V1 Air Conditioner Accessories?
- TthomaskaraOct 31, 2025
If you're experiencing a lack of Modbus communication with your Daikin Air Conditioner Accessories, it might be due to an incorrect Modbus address setting at power on. To resolve this, power off the system and set DS2 according to the required Modbus address, referring to chapter “1.3.6 Dipswitch meaning”. Remember that the dipswitch on/off status is only detected when the PCB powers on. Alternatively, if no Modbus address setting is configured (DS2 is set to Off/Off/Off/Off), set DS2 according to the required Modbus address. See chapter “1.3.6 Dipswitch meaning”. Another potential cause is if only the firmware is present on the Modbus Interface DIII, indicated by the HAP blinking rapidly at 200ms. In this case, upload the latest application software, as detailed in chapter “4.2 Software...







