Table 6: 003–015 Electric Heat Data
1
kW Voltage Amps kW Voltage Amps
6
208 16.7
36
208 99.9
230 15.1 230 90.4
475 7.3 475 43.8
575 6.0 575 36.1
12
208 33.3
54
208 149.9
230 30.1 230 135.6
475 14.6 475 65.6
575 12.0 575 54.2
18
208 50.0
72
208 N/A
230 45.2 230 N/A
475 21.9 475 87.5
575 18.1 575 72.3
30
208 83.3
230 75.3
475 36.5
575 30.1
NOTE: 1. Maximum temperature rise equals 60ºF
Table 7: DPS 016–028 Electric Heat Data
KW Voltage Amps KW Voltage Amps
30
208 83.4
90
208 250.1
230 75.4 230 226.2
460 37.7 460 113.1
575 30.2 575 90.5
45
208 125.1
120
208 333.5
230 113.1 230 301.6
460 56.5 460 150.8
575 45.2 575 120.6
60
208 166.7
150
208 416.9
230 150.8 230 377.0
460 75.4 460 188.5
575 60.3 575 150.8
Table 8: Amp Draw Data
Unit
Size
(Tons)
Compressor RLA Compressor LRA
Condenser Fan
FLA Each
Compressor 1 - Variable Compressor 2 - Fixed Compressor 1 Compressor 2
Qty 208 230 460Voltage Voltage Voltage Voltage
208 230 460 575 [%] 208 230 460 575 208 230 460 575 208 230 460 575
3 7.7 7.0 3.5 45% 0.0 0.0 0.0
See Note
0.0 0.0 0.0 1 0.9 0.8 0.4
4 10.0 9.0 4.5 55% 0.0 0.0 0.0 0.0 0.0 0.0 1 0.9 0.8 0.4
5 11.9 10.8 5.4 68% 0.0 0.0 0.0 0.0 0.0 0.0 1 2.0 1.8 0.9
6 15.0 13.6 6.8 89% 0.0 0.0 0.0 0.0 0.0 0.0 1 2.0 1.8 0.9
7.5 11.9 10.8 5.4 68% 8.6 7.8 3.9 67.5 73.7 37.1 2 2.0 1.8 0.9
10 10.0 9.0 4.5 59% 17.5 15.8 7.9 93.1 84.2 42.1 2 2.0 1.8 0.9
12 15.0 13.6 6.8 89% 17.5 15.8 7.9 93.1 84.2 42.1 2 2.0 1.8 0.9
15 28.3 25.6 12.8 100% 17.5 15.8 7.9 93.1 84.2 42.1 2 2.0 1.8 0.9
16 47.0 42.5 22.9 20.5 0 0 0 0
See Note
1 8.0 8.0 4.0
18 47.0 42.5 22.9 20.5 0 0 0 0 1 8.0 8.0 4.0
20 47.0 42.5 22.9 20.5 0 0 0 0 1 8.0 8.0 4.0
25 47.0 42.5 22.9 20.5 39.1 35.4 18.6 15.4 1 8.0 8.0 4.0
28 47.0 42.5 22.9 20.5 39.1 35.4 18.6 15.4 1 8.0 8.0 4.0
NOTE: The inverter compresor is controlled to have a soft start and an LRA <1.0
Horse
Power
Supply Fan FLA (DPS 003–015) Exhaust Fan FLA (DPS 003–028) Supply Fan FLA (016–028)
Voltage Voltage Voltage
208 230 460 kW 208 230 460 kW 208 230 460 575
1.3 3.1 2.8 1.4 1.0 3.1 2.8 1.4 1.0
2.3 5 4.6 2.3 1.7 5 4.6 2.3 1.7
3 9.9 9.0 4.5 3.4
4 8.8 7.4 4.0 3.0 8.8 7.4 4.0 3.0
5 16.1 14.0 7.0 5.3
7.5 25.0 21.6 10.8 8.2
8 13.5 12.2 6.1 6.0
10 33.0 28.0 14.0 11.0
15 44.8 40.6 20.3 16.2
20 61.0 50.0 25.0 20.0
NOTE: DPS 007–015 575V Amp Draws: Compressors and motors will be run off a 575 to 460V transformer. Motors will be nameplated at 460V.
EAF FLA are per motor. Some DPS 016028 units have (2) EAFs and motors.