2 | Troubleshooting
Service manual
48
EBLA09~16DA + EDLA09~16DA
Daikin Altherma 3 M
ESIE20-06A – 2021.03
Trigger Effect Reset
Outdoor heat exchanger
thermistor input is out of
range.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the heat exchanger thermistor. See
"3.20Thermistors"[4248].
Possible cause: Faulty heat exchanger thermistor.
2 Perform a check of the main PCB. See "3.14Main PCB"[4171].
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.53 J6-07 – Outdoor unit: Malfunction of heat exchanger thermistor
Trigger Effect Reset
Heat exchanger
thermistor input is out of
range.
Unit will stop operating. Manual reset via user
interface.
To solve the error code
INFORMATION
It is recommended to perform the checks in the listed order.
1 Perform a check of the heat exchanger (middle) thermistor. See
"3.20Thermistors"[4248].
Possible cause: Faulty heat exchanger (middle) thermistor.
2 Perform a check of the main PCB. See "3.14Main PCB"[4171].
Possible cause: Faulty main PCB.
INFORMATION
If all procedures listed above have been performed and the problem is still present,
contact the helpdesk.
2.3.54 J6-32 – Leaving water temperature thermistor abnormality (outdoor unit)
Trigger Effect Reset
Temperature sensor after
plate type heat exchanger
is broken.
Unit will NOT stop
operating.
Automatic reset.