EasyManua.ls Logo

Daikin EKHBRD011AAV1 - User Manual

Daikin EKHBRD011AAV1
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
OPERATION MANUAL
EKHBRD011AAV1
EKHBRD014AAV1
EKHBRD016AAV1
EKHBRD011AAY1
EKHBRD014AAY1
EKHBRD016AAY1
Indoor unit for air to water heat pump system
and options

Other manuals for Daikin EKHBRD011AAV1

Questions and Answers

  • R
    Rodney WigginsAug 12, 2025
    Why is my Daikin EKHBRD011AAV1 not heating properly even when it's on?
    • H
      Holly TorresAug 12, 2025
      If your Daikin Heat Pump isn't heating as expected, even when turned on, there are several things you can check: * Ensure the temperature setting on the controller is correct. * Verify that all shut-off valves in the water circuit are fully open and clean the water filter if needed. * Purge any air from the system. * Check the manometer to confirm sufficient water pressure (greater than 0.3 bar when the water is cold, and significantly greater when hot). * Confirm the expansion vessel is not broken. * Also, ensure the water volume in the installation is above the required minimum. Finally, check if the cooling fans at the rear of the switch box are working properly.
  • A
    Albert BarnettAug 16, 2025
    Why is my Daikin EKHBRD011AAV1 Heat Pump schedule timer running late?
    • D
      Dana MitchellAug 16, 2025
      The programmed actions might be executed at the wrong time because the clock and the day of the week are not set correctly. Verify these settings and correct them if necessary.
  • M
    Marco OconnorAug 19, 2025
    What to do if the Daikin Heat Pump domestic hot water schedule timer isn't working?
    • S
      Shannon RobinsonAug 19, 2025
      If the pr icon is not displayed, push the pr button to enable the schedule timer.
  • S
    Shannon FuentesAug 25, 2025
    Why is my Daikin Heat Pump pump making noise?
    • M
      Mary CarrollAug 25, 2025
      If your Daikin Heat Pump pump is making noise (cavitation), it could be due to air in the system. Try purging the air. Another cause might be low water pressure at the pump inlet. Check the manometer to ensure sufficient water pressure (greater than 0.3 bar when the water is cold, and significantly greater when hot). Also, verify the manometer and expansion vessel aren't broken and that the expansion vessel's pre-pressure setting is correct.
  • W
    William WalshAug 27, 2025
    How to fix a blank display on my Daikin EKHBRD011AAV1 remote controller?
    • C
      cindyherreraAug 27, 2025
      First, check if the mains power is still connected to your installation. Also, verify if the benefit kWh rate power supply is active.
  • R
    Ryan McintoshAug 30, 2025
    Why does the water pressure relief valve open on my Daikin EKHBRD011AAV1 Heat Pump?
    • J
      Jennifer KaneAug 31, 2025
      If the water pressure relief valve on your Daikin Heat Pump opens, it could be because the expansion vessel is broken, in which case you should replace it. Alternatively, the water volume in the installation might be too high. Ensure the water volume is under the maximum allowed value.
  • G
    Gary NelsonSep 3, 2025
    What to do if the water pressure relief valve leaks in my Daikin EKHBRD011AAV1 Heat Pump?
    • C
      Christina JohnsonSep 3, 2025
      If the water pressure relief valve on your Daikin Heat Pump leaks, it might be due to dirt blocking the valve outlet. Check the pressure relief valve by turning the red knob counter-clockwise. If you don't hear a clacking sound, the unit requires servicing. If water continues to run out, close both the water inlet and outlet shut-off valves.
  • B
    Brittany FreemanSep 7, 2025
    Why does my Daikin EKHBRD011AAV1 Heat Pump display 'nnnn' when I press certain buttons?
    • R
      Robert DiazSep 7, 2025
      If your Daikin Heat Pump user interface displays "nnnn" when pressing certain buttons, the current permission level might be set too low to allow the use of that button. Change the "user permission level" field setting.

Overview

This document is an operation manual for the Daikin EKHBRD011AAV1, EKHBRD014AAV1, EKHBRD016AAV1, EKHBRD011AAY1, EKHBRD014AAY1, and EKHBRD016AAY1 indoor units, which are part of an air-to-water heat pump system and its options. The manual provides detailed instructions on how to operate, maintain, and troubleshoot the unit.

Function Description

The Daikin EKHBRD indoor unit is designed for floor-standing indoor installation and is primarily used for heating applications. It functions as the indoor component of an air-to-water ERSQ or ERRQ heat pump system. The unit can be integrated with space heating radiators (field supply) and an optional EKHTS domestic hot water tank. A remote controller with room thermostat functionality is standard supplied to control the installation.

The unit supports various operation modes for space heating and domestic water heating, including:

  • Space Heating Operation: Can be controlled based on room temperature or leaving water temperature.
  • Domestic Water Heating Operation: Offers automatic storage (daily heat-up), manual storage (one-time heat-up), reheat (continuous minimum temperature maintenance), and disinfection operations.
  • Schedule Timer Operation: Allows users to program specific actions for space heating, domestic water heating, and quiet mode at scheduled times.
  • Quiet Mode Operation: Reduces compressor speed to lower noise levels, which may extend the time required to reach the desired temperature set point.
  • Defrost Operation: Automatically activates to prevent freezing of the outdoor heat exchanger in low outdoor temperatures.
  • Emergency Operation: In this mode, heating is exclusively done by the heater kit, bypassing the heat pump.

Important Technical Specifications

The manual refers to a "Field settings table" (pages 16-18) which lists various parameters and their default values, ranges, and units. Key specifications include:

  • Temperature Ranges:
    • Room temperature for heating: 16°C to 32°C.
    • Leaving water temperature for heating: 25°C to 80°C.
    • Weather-dependent set point: Low ambient temperature (Lo_A) from -20°C to 5°C, High ambient temperature (Hi_A) from 10°C to 20°C.
    • Disinfection operation temperature: 60°C to 75°C.
    • Hot water storage temperature: 45°C to 75°C.
    • Reheat minimum water temperature: 35°C to 65°C.
    • Reheat maximum water temperature: 35°C to 75°C.
    • Leaving water maximum temperature: 37°C to 80°C.
    • Leaving water minimum temperature: 25°C to 37°C.
  • Time Settings:
    • Night time storage start time: 0:00 to 23:00 (1-hour step).
    • Day time storage start time: 0:00 to 23:00 (1-hour step).
    • Setback operation start/stop time: 0:00 to 23:00 (1-hour step).
    • Disinfection operation start time: 0:00 to 23:00 (1-hour step).
    • Disinfection operation time duration: 5 to 60 minutes (5-minute step).
    • Minimum time for domestic water heating: 5 to 20 (1-unit step).
    • Maximum time for domestic water heating: 10 to 60 (5-unit step).
    • Interval minimum stop time of domestic water heating: 5 to 30 (5-unit step).
  • Refrigerant: R134a, with a GWP (Global Warming Potential) value of 1300.

Usage Features

  • Remote Controller: The unit is operated via a remote controller with a room thermostat function. It provides full control over heating applications, varying in capacity, electrical supply, and installed equipment.
  • Clock and Day Setting: Users can manually set the clock and day of the week, which is essential for the schedule timer to function correctly. A power failure exceeding 1 hour will reset these settings.
  • Space Heating Control:
    • Room Temperature Control: Heating activates based on a user-defined room temperature set point, which can be set manually or via the schedule timer. This mode prioritizes room temperature control over leaving water control.
    • Leaving Water Temperature Control: Heating activates based on a water temperature set point, which can be set manually, through the schedule timer, or automatically via weather-dependent operation.
    • Automatic Setback Function: Lowers the room temperature during specific periods (e.g., at night) to optimize energy consumption.
    • Weather Dependent Set Point Operation: Automatically adjusts the leaving water temperature based on outdoor temperature, leading to lower power consumption. Users can shift the target water temperature by a maximum of ±5°C.
  • Domestic Water Heating Control:
    • Automatic Storage: Heats water to a set point during the night (when space heating requirements are lower) and/or during the day, based on a daily fixed pattern.
    • Manual Storage: Allows immediate, one-time heating of water to a set point.
    • Reheat Function: Maintains the domestic hot water tank temperature above a minimum value.
    • Disinfection Operation: Periodically heats the domestic water to a specific temperature to disinfect the tank.
  • Schedule Timer: Enables programming of up to five actions per day for space heating, domestic water heating, and quiet mode. Actions can be based on temperature set points or ON/OFF instructions.
  • Temperature Read-out Mode: Allows users to view actual temperatures, including leaving water, entering water, indoor, outdoor, and hot water supply tank temperatures.
  • Field Settings: Advanced configuration of the Daikin system parameters is done through field settings, accessible via the user interface.

Maintenance Features

  • Regular Checks: To ensure optimal availability, yearly checks and inspections of the unit and field wiring should be carried out by a local Daikin technician.
  • Operator Maintenance:
    • Keep the remote controller clean with a soft damp cloth.
    • Check if the water pressure indicated on the manometer is above 1 bar.
  • Power Supply: It is crucial NOT to switch off the power supply to the unit during longer periods of standstill (e.g., summer for heating-only applications) to prevent the pump from getting jammed due to repetitive movement.
  • Refrigerant Leak Inspections: Periodical inspections for refrigerant leaks may be required based on European or local legislation. Users should contact their local dealer for more information.
  • Troubleshooting Guidelines: The manual provides a troubleshooting section to help users solve common problems, such as no readings on the remote controller, error codes, incorrect schedule timer execution, or capacity shortage. For complex issues, users are advised to consult their installer or local dealer.
  • Disposal Requirements: Dismantling, treatment of refrigerant, oil, and other parts must be done by a qualified installer in accordance with relevant local and national legislation. The unit should be treated at a specialized treatment facility for re-use, recycling, and recovery.

Daikin EKHBRD011AAV1 Specifications

General IconGeneral
BrandDaikin
ModelEKHBRD011AAV1
CategoryHeat Pump
LanguageEnglish

Related product manuals