5 | Application guidelines
Installer reference guide
28
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12
5.2.1 Single room
Underfloor heating or radiators – Wired room thermostat
Setup
A Main leaving water temperature zone
B One single room
a Dedicated Human Comfort Interface (BRC1HHDA used as room thermostat)
▪ For more information about connecting the electrical wiring to the unit, see:
- "8.2Connections to the outdoor unit"[491]
- "8.3Connections to the indoor unit"[498]
▪ The underfloor heating or radiators are directly connected to the indoor unit.
▪ The room temperature is controlled by the dedicated Human Comfort Interface
(BRC1HHDA used as room thermostat).
Configuration
Setting Value
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
2 (Room thermostat): Unit operation
is decided based on the ambient
temperature of the dedicated Human
Comfort Interface.
Number of water temperature zones:
▪ #: [4.4]
▪ Code: [7-02]
0 (Single zone): Main
Benefits
▪ Highest comfort and efficiency. The smart room thermostat functionality can
decrease or increase the desired leaving water temperature based on the actual
room temperature (modulation). This results in:
- Stable room temperature matching the desired temperature (higher comfort)
- Less ON/OFF cycles (more quiet, higher comfort and higher efficiency)
- Lowest possible leaving water temperature (higher efficiency)
▪ Easy. You can easily set the desired room temperature via the user interface:
- For your daily needs, you can use preset values and schedules.
- To deviate from your daily needs, you can temporarily overrule the preset
values and schedules, or use the holiday mode.