5 | Application guidelines
Installer reference guide
45
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12
5.4.5 DHW pump for disinfection
Setup
a Cold water IN
b Hot water OUT (shower (field supply))
c DHW pump (field supply)
d Heater element (field supply)
e Non‑return valve (field supply)
▪ The DHW pump is field-supplied and its installation is the responsibility of the
installer. For the electrical wiring, see "To connect the domestic hot water
pump"[4107].
▪ If the applicable legislation requires a higher temperature than the maximum
tank setpoint during disinfection (see [2-03] in the field settings table), you can
connect a DHW pump and heater element as shown above.
▪ If applicable legislation requires disinfection of the water piping until the tapping
point, you can connect a DHW pump and heater element (if needed) as shown
above.
Configuration
The indoor unit can control DHW pump operation. For more information, see
"9Configuration"[4115].
5.5 Setting up the energy metering
▪ Via the user interface, you can read out the following energy data:
- Produced heat
- Consumed energy
▪ You can read out the energy data:
- For space heating
- For space cooling
- For domestic hot water production
▪ You can read out the energy data:
- Per month
- Per year