8 | Electrical installation
Installer reference guide
96
EPRA14~18DAV3+W1 + ETVH/X16S18+23DA6V+9W(G)
Daikin Altherma 3 H HT F
4P587502-1B – 2020.12
1 2 3
1
2
3
3 (Optional) Drain tube heater cable:
Make sure the heating element of the drain tube heater is completely inside
the drain tube.
Route the cable through the frame.
Connect the wires to the terminal block and the earth screw.
Fix the cable with cable ties.
Wires: (2+GND)×0.75mm². Wiring must be double insulated.
Maximum power allowed for drain tube heater = 115W (0.5A)