The Digital Controller ESIE10-01
2–18 Part 2 – Functional Description
3
1
2
4
5
The following set points exist individually for each circuit:
Slide Load Delay Maximum 150 seconds 60 to 300 seconds
Slide Unload Delay Minimum 10 seconds 5 to 20 seconds
Slide Unload Delay Maximum 50 seconds 30 to 75 seconds
Liquid Injection Activation 85°C 75 to 90°C
Liquid Line Solenoid Valves No No, Yes
Alarm Limits SI
Low Evap Pressure-Unload 190 KPA See auto adjusted settings
Low Evap Pressure-Hold 200 KPA See auto adjusted settings
Oil Press Delay 30 sec 10-180 sec
Oil Press Differential 250 KPA 0 to 415 KPA
Low Oil Level Delay 120 sec 10 to 180 sec
High Discharge Temperat. 110°C 65 to 110°C
High Lift Pressure Delay 5 sec 0 to 30 sec
Low Pressure Ratio Delay 90 sec 30-300 sec
Start Time Limit 60 sec 20 to 180 sec
Evaporator Water Freeze 2.2°C See auto adjusted settings
Evaporator Flow Proof 15 sec 5 to 15 sec
Recirculate Timeout 3 min 1 to 10 min
Low Ambient Lockout Enable Disable Disable, Enable
Low Ambient Lockout 12°C See auto adjusted settings
Description Default Range
SI
Circuit mode Enable Disable, enable, test
Compressor Size To be Veri-
fied
Capacity Control Auto Auto, Manual
Manual Capacity See note 1
below table
0 to 100%
Clear Cycle Timers No No, yes
EXV control Auto Auto, manual
EXV position See note 2
below table
0 to 100%
Oil Sump Check Enable Enable, Disable
Service Pumpdown No No, Yes
Evap pressure offset 0 KPA -100 to 100 KPA