The Digital Controller ESIE10-01
2–20 Part 2 – Functional Description
3
1
2
4
5
Auto adjusted
ranges
Some settings have different ranges of adjustment based on other settings.
Cool LWT 1 and Cool LWT 2
Evaporator Water Freeze
Low Evaporator Pressure - Hold
Low Evaporator Pressure - Unload
Low Ambient Lockout
Available Mode Selection Range SI
Without Glycol 4 to 15°C
With Glycol -4 to 15°C
Available Mode Selection Range SI
Without Glycol 2 to 6°C
With Glycol -18 to 6°C
Available Mode Selection Range SI
Without Glycol 195 to 310 KPA
With Glycol 0 to 310 KPA
Available Mode Selection Range SI
Without Glycol 180 to 310 KPA
With Glycol 0 to 410 KPA
Fan VFD Range SI
= no for all circuits 2 to 15°C
= yes on any circuit -23 to 15°C