Running Data ESIE10-01
4–10 Part 4 – Commissioning and Test Run
3
1
4
5
2.2 Typical Operating Data
Standard eff with
ST/LN
Nominal Conditions: OAT 35°C – Ent/Leav. Water Temp. 12/7°C – 100%
High eff with ST/LN Nominal Conditions: OAT 35°C – Ent/Leav. Water Temp. 12/7°C
Premium eff with
ST/LN
Nominal Conditions: OAT 35°C – Ent/Leav. Water Temp. 12/7°C
Operating Value Standard Noise Low Noise
Condensing Temperature 52-53°C 54-56°C
Evaporating Temperature 2-3°C 2-3°C
Total Liquid Sub Cooling 4-6°C 4-6°C
Suction Superheat 4-6°C 4-6°C
Discharge Superheat 20-25°C 20-25°C
Operating Value Standard Noise Low Noise
Condensing Temperature 50-52°C 53-55°C
Evaporating Temperature 2-4°C 2-4°C
Total Liquid Sub Cooling 19-24°C 19-24°C
(Cond. Coil 4-6°C – Eco 15-18°C)
Suction Superheat 4-6°C 4-6°C
Economiser Superheat 5-8°C 5-8°C
Discharge Superheat 20-25°C 20-25°C
Operating Value Standard Noise Low Noise
Condensing Temperature 48-50°C 50-52°C
Evaporating Temperature 4-5°C 4-5°C
Total Liquid Sub Cooling 19-24°C 19-24°C
(Cond. Coil 4-6°C – Eco 15-18°C)
Suction Superheat 4-6°C 4-6°C
Economiser Superheat 5-8°C 5-8°C
Discharge Superheat 20-25°C 20-25°C

Related product manuals