2.2.5 Ice Mode Start Delay
An adjustable start to start ice delay timer will limit the frequency with which the chiller may start in Ice
mode. The timer starts when the first compressor starts while the unit is in ice mode. While this timer
is active, the chiller cannot restart in Ice mode. The time delay is user adjustable.
The ice delay timer may be manually cleared to force a restart in ice mode. A set point specifically for
clearing the ice mode delay is available. In addition, cycling the power to the controller should clear
the ice delay timer.