Alarms and Events ESIE10-01
3–16 Part 3 – Troubleshooting
3
1
3
4
5
1.3.2 External Event
Alarm description (as shown on screen): External Event.
Trigger: External Alarm/Event input is open for at least 5 seconds and external fault is configured as
an event.
Action Taken: None.
Reset: Auto clear when digital input is closed.