ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–19
33
4
5
1
1.4.1 Phase Volts Loss/GFP Fault
Alarm description (as shown on screen): PVM/GFP Fault N.
Trigger: PVM input is low and PVM set point = Multi Point.
Action Taken: Rapid stop circuits.
Reset: Auto reset when PVM input is high or PVM set point does not equal multi point for at least 5
seconds.