ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–21
33
4
5
1
1.4.3 Low Pressure Start Fail
Alarm description (as shown on screen): LowPressStartFail N.
Trigger: Circuit state is in the 'start'-status for time greater than Startup Time set point.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.