ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–23
33
4
5
1
1.4.5 High Condenser Pressure
Alarm description (as shown on screen): Cond Pressure High N.
Trigger: Condenser Saturated Temperature is higher than the Max Saturated Condenser Value for
time longer than High Cond Delay set point.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.
Setpoint
20.5
HP Alarm
If HP is below
this value
possible
to reset
15.5
HP
Time