Alarms and Events ESIE10-01
3–28 Part 3 – Troubleshooting
3
1
3
4
5
1.4.10 Compressor Starter Fault
Alarm description (as shown on screen): Starter Fault N.
Trigger:
If PVM set point = None(SSS): any time starter fault input is open.
If PVM set point = Single Point or Multi Point: compressor has been running for at least 14 seconds
and starter fault input is open.
Action Taken: Rapid stop circuit.
Reset: This alarm can be cleared manually via the Unit Controller keypad.