ESIE10-01 Alarms and Events
Part 3 – Troubleshooting 3–33
33
4
5
1
1.4.15 CC Comm Failure N
Alarm description (as shown on screen): CC Comm. Fail N.
Trigger: Communication with the I/O extension module has failed.
Action Taken: Rapid stop of affected circuit.
Reset: This alarm can be cleared manually via the keypad when communication between main
controller and the extension module is working for 5 seconds.