Alarms and Events ESIE10-01
3–38 Part 3 – Troubleshooting
3
1
3
4
5
1.4.20 EEXV Comm Failure N
Alarm description (as shown on screen): EEXV Comm. Fail N.
Trigger: Communication with the I/O extension module has failed. Alarm on Circuit #3 will be enabled
if Number of Circuits set point > 2; alarm on Circuit #4 will be enabled if Number of Circuits set point
> 3.
Action Taken: Rapid stop of affected circuit.
Reset: This alarm can be cleared manually via the keypad when communication between main
controller and the extension module is working for 5 seconds.