ESIE10-01 Controller Inputs and Outputs
Part 3 – Troubleshooting 3–57
33
4
5
1
Digital outputs
# Description Output OFF Output ON
DO1 Evaporator Water Pump Pump Off Pump On
DO2 Unit Alarm Alarm not Active Alarm Active (Flashing= circuit alarm)
DO3 Circuit #1 Fan Step #1 Fan Off Fan On
DO4 Circuit #1 Fan Step #2 Fan Off Fan On
DO5 Circuit #1 Fan Step #3 Fan Off Fan On
DO6 Circuit #1 Fan Step #4 Fan Off Fan On
DO7 Circuit #2 Fan Step #1 Fan Off Fan On
DO8 Circuit #2 Fan Step #2 Fan Off Fan On
DO9 Circuit #2 Fan Step #3 Fan Off Fan On
DO10 Circuit #2 Fan Step #4 Fan Off Fan On