General Outline ESIE10-01
1–52 Part 1 – System Outline
3
11
4
5
1.21 Electrical Specifications: EWAD~C-PL
Electrical
specifications
The table below contains the electrical specifications
Model EWAD~C-PL
820 890 980 C11 C12 C13 C14
Power Supply Phase 3
Frequency Hz 50
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Unit Maximum starting current A 660.4 697.2 697.2 936.2 981.8 1041 1049
Nominal running current cooling A 384 420 461 506 551 609 665
Maximum running current A 518 564 610 675 732 804 876
Maximum current for wires siz-
ing
A 570 620 671 743 805 884 964
Fans Nominal running current in cool-
ing
A 72 72 72 80 80 88 96
Compressor Phase No. 3
Voltage V 400
Voltage Tolerance Minimum % -10%
Maximum % +10%
Maximum running current A 223
+223
223
+269
269
+269
269
+326
326
+326
390
+326
390
+390
Starting Method Wye - Delta type (Y -Δ)