EWAQ016~064BAW + EWYQ016~064BAW
Packaged air-cooled water chiller
4PW70082-1C – 2013.07
Installation and operation manual
40
A Option setup
00 Not applicable. Do not change the default value.
0—
01 Not applicable. Do not change the default value.
0—
02 Not applicable. Do not change the default value.
5—
03 Allowable overshoot on leaving water
3 1~5 0.5 °C
04 Ethylene glycol concentration
0 0~1 1
b Settings are not applicable
00 Not applicable. Do not change the default value.
35
01 Not applicable. Do not change the default value.
45
02 Not applicable. Do not change the default value.
1—
03 Not applicable. Do not change the default value.
70
04 Not applicable. Do not change the default value.
70
C Leaving water temperature limits
00 Set point: heating leaving water maximum
temperature
50 37~50 1 °C
01 Set point: heating leaving water minimum
temperature
25 25~37 1 °C
02 Set point: cooling leaving water maximum
temperature
20 18~22 1 °C
03 Set point: cooling leaving water minimum
temperature
5Q
(a)
~18 1 °C
04 Not applicable. Do not change the default value.
0—
d Settings are not applicable
00 Not applicable. Do not change the default value.
10
01 Not applicable. Do not change the default value.
30
02 Not applicable. Do not change the default value.
15
03 Not applicable. Do not change the default value.
15
04 Not applicable. Do not change the default value.
40
E Service mode
00 Not applicable. Do not change the default value.
0—
01 Not applicable. Do not change the default value.
0—
02 Not applicable. Do not change the default value.
0—
03 Not applicable. Do not change the default value.
1—
04 Pump only operation
0 0~25 1
F Settings are not applicable
00 Not applicable. Do not change the default value.
5—
01 Not applicable. Do not change the default value.
0—
02 Not applicable. Do not change the default value.
1—
03 Not applicable. Do not change the default value.
10
04 Not applicable. Do not change the default value.
50
(a) Refer to page 21 where [C-03] is explained.
First
code
Second
code
Setting name
Installer setting at variance with default value
Default
value
Range Step UnitDate Value Date Value
4PWEN70082-1C.book Page 40 Wednesday, September 25, 2013 7:31 AM