Water supply
Check if the water connection is still well fixed.
Check the water quality (refer to the installation manual of the unit
for specifications of the water quality).
Water filters
Make sure to clean the water filter in front of the evaporator water
inlet once every 4 months.
Check the filter for any possible damage and make sure that the
hole diameter size all over the filter surface is still 1.0 mm
maximum.
Water sensors
Check that all the water sensors are correctly fixed into the inlet
and outlet water pipe.
Flowswitch
Make sure that there is no dirt accumulating on the paddle of the
flowswitch.
Water pressure
Check if the water pressure is within acceptable range. Refer to
the installation manual delivered with the unit.
Disposal requirements
Dismantling of the unit, treatment of the refrigerant, of oil and of other
parts must be done in accordance with relevant local and national
legislation.