Daikin FAY71LVE - 3.97 U9 Transmission Error Between Indoor and Outdoor Units in the Same System

Daikin FAY71LVE
501 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Si20-701_B Troubleshooting by Remote Controller
414
External control adaptor for outdoor unit
•Is this PCB energized?
•Does the cool/heat unified address match?
Outdoor unit (unified master unit)
•Is this energized?
•Does the cool/heat unified address match?
Does an
error occur when
the cool / heat selector
is set to "IND?"
Replace the
external control
adaptor for
outdoor unit.
Replace the
outdoor unit PCB
(A1P).
NO
A
B
YES
YES