Connection information on power supply wiring, earth wiring, and transmission wiring
〉
For the indoor unit wiring and transmission wiring (dash lines in the drawing), follow the instructions in the
indoor unit’s installation manual.
〈
Specification of standard wiring components
〉
NOTES
1. Order appropriate power wire while following national laws and standards for the insulating sheath,
thickness, and length.
2. When installing wiring in a location that can easily come in contact with people, be sure to install an earth
leakage breaker to prevent electric shock.
3. The earth leakage breaker must be a high-speed type breaker of 30mA(<0.1S).
4. Use an earth leakage breaker that can also be used as earth leakage, overload, short-circuit protection.
Be sure to use earth leakage breakers dedicated for earth leakage protection in combination with the load
break switch with fuse or breaker for wiring.
5. RZR48MUYMK is
only 50Hz model.
〈
CAUTION
〉
To the electrician
Do not run the unit until the refrigerant piping is complete, as not waiting could break the compressor.
POWER SUPPLY
50Hz/60Hz
1 2 3
1 2 3
L
N
NL
TINU ROODTUO
TINU ROODTUO
Earth leakage
breaker
Branch switch,
Power supply wire
(60245 IEC 57)
overcurrent
breaker
INDOOR UNIT
Remote Controller
INDOOR UNIT
Remote Controller
POWER SUPPLY
380-415V/400V
50Hz/60Hz
3N~
220-240V/230V
1~
brea
1 2 3
1 2 3
L1 L2 L3 N
L1 L2 L3 N
Earth leakage
breaker
Branch switch,
overcurrent
breaker
RZ(Q/R)
YV
20
Minimum circuit amps (MCA) 18.8 28.2 16.7
Recommended field fuse (A)
Power supply wire
diameter(mm²)
32 20
14.9
16
20
4.0 or more 2.5 or more2.5 or more
24 36 45 45 48
V
Y
Power supply wire
(60245 IEC 57)