Outdoor Unit: 80/90 Class SiBE121135
392 Removal Procedure
2.4 Removal of Fan Motor
Procedure Warning Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Step
Procedure Points
1
2
Remove the 2 lower
screws of the fan motor.
Remove the 2 upper
screws.
Be sure to remove the lower
screws first. If the upper
screws are removed first, the
fan motor may tilt or fall
because the center of its
gravity is toward the front.
It may cause injuries.
3 Remove the fan motor. When reassembling, be sure
to place the wire harness
lower.
(R10414)
(R6442)
2
1
(R10542)
Fan motor
(R6444)
Harness