SiBE121135 Outdoor Unit: 80/90 Class
Removal Procedure 397
7
Remove the discharge
pipe thermistor.
8
Remove the fixture.
3. Remove the four way
valve coil.
1
Remove the screw.
Step
Procedure Points
(R10420)
Discharge pipe thermistor
(R10430)
Fixture
(R10431)